The Quelfire QuelStop Intumescent Fire Pillow is a flexible, removable firestop solution designed for use inside steel cable trunking systems that pass through fire compartment walls. Filled with organic materials and intumescent additives, these pillows expand under heat to seal voids, preventing fire and smoke from spreading.

Ideal for retrofit and temporary firestopping, they can be easily installed or removed without compromising performance. Each pillow is wrapped in a moisture-resistant glass cloth case, offering durability and temperature resistance from -20°C to +130°C.

Tested in accordance with BS EN 1366-3:2009, these CE-compliant fire pillows deliver up to 60 minutes of fire integrity, providing a fast, compliant solution for cable containment routes.


Key Features & Benefits

  • Up to 60 minutes fire integrity

  • Tested to BS EN 1366-3:2009

  • Suitable for steel cable trunking (up to 150mm x 150mm)

  • Can be used in flexible or rigid walls

  • Available in 3 sizes for full flexibility

  • Simple to install, reposition, or remove

  • Moisture-resistant, high-temperature glass cloth casing

  • Compatible with QuelStop Acrylic Sealant for full seal

  • No shelf life if stored in cool, dry conditions

  • Remains effective between -20°C and +130°C


Sizes Available

Product Code Description Dimensions (mm) Weight
QFP1 Small 330 x 50 x 20 50g
QFP2 Medium 330 x 200 x 25 185g
QFP3 Large 330 x 200 x 45 385g

Installation Guidance

  • Ensure trunking and cables are clean and dust-free

  • Place pillows lengthways in steel trunking

  • Stagger joints and compress pillows tightly to fill voids

  • Centrally position within the wall thickness

  • Fill remaining gaps around trunking with backing rod and seal with QuelStop Intumescent Acrylic Sealant to a 10mm depth

  • Maximum cable fill: 60% of trunking volume

  • Max tested trunking size: 150mm x 150mm (wall aperture max 170mm x 170mm)


Applications

  • Firestopping cable trunking in service risers

  • Retrofit fire protection in trunking penetrations

  • Temporary sealing of trunking during construction

  • Buildings requiring demountable firestop solutions