The Quelfire QWR CE Marked Fire Collar is a vital fire protection solution designed to reinstate the fire resistance of walls and floors where plastic pipes pass through compartment lines. It is suitable for PVC, PVC-U, PE, HDPE, MDPE, and PP pipes, with sizes ranging from 25mm to 160mm.

Each collar features a flexible stainless steel shell containing graphite-based intumescent material that expands in the presence of heat to create a carbonised seal. This seals the opening as the plastic pipe softens and melts, preventing the passage of fire and smoke. The collar comes with built-in fixing lugs for secure installation and is tested to BS EN 1366-3:2009, with fire resistance up to 4 hours.

Tested for Type X Durability, the QWR Fire Collar is suitable for internal and external applications, even where exposed to weathering.


Key Features

  • Tested to BS EN 1366-3:2009

  • Classified to EN 13501-2:2007 + A1:2009

  • CE Marked with ETA 16/0556

  • Up to 4-hour fire rating (depending on pipe size)

  • Pipe compatibility: PVC, PVC-U, PE, HDPE, MDPE, PP

  • Range: For 25mm to 160mm pipe diameters

  • Suitable for walls and floors

  • Retrofittable for remedial applications

  • Built-in fixing lugs – secure with sleeve anchors or through-bolts

  • Type X Durability – unaffected by weather exposure

  • Expected to last the life of the building


Specifications

  • Product Code: QWR25/CE – QWR125/CE/2

  • Pipe Sizes: 25mm to 160mm

  • Fire Resistance: Up to 240 minutes (120 minutes for some variants)

  • Composition: Stainless steel casing with graphite-based intumescent insert

  • Installation: Around pipework in walls/floors, fixed via integral lugs

  • Approvals: ETA 16/0556, CE Marked

  • Durability: Type X rated for weather-exposed applications

  • Tested in England under Warringtonfire certification


Installation Notes

  • Install one unit beneath floor penetrations or on both sides of wall penetrations

  • For plasterboard partitions, install collars on both sides using through-bolts or cavity anchors

  • Surfaces should be smooth; any gaps filled with Quelfire GM Acrylic Sealant

  • Collars wrap around pipes and secure with integrated lugs

  • Must be fixed using steel sleeve anchors or approved fixings for your substrate